QAS 5 100
Trailerised QAS 5 100
Feature |
QAS 5 80 |
QAS 5 120 |
Rated Frequency |
50 | 60hz |
50 | 60hz |
Rated Voltage |
400 | 480V |
400 | 480V |
Prime Power Output |
80/64 | 88/70Kva |
8 124/99 | 132/106Kva |
Peak Power Output |
88/70 | 97/78Kva |
138/110 | 146/117Kva |
Rated Current |
115 | 106A |
179 | 159A |
Power Factor cos Phi |
0.8 |
0.8 |
Operating temperature (min/max) |
-25 / 50ºC |
-25 / 50ºC |
Fuel Tank Capacity |
392L |
392L |
Fuel Autonomy @ 100% |
22h |
17h |
Fuel Consumption @ 75%
|
13.9L/h |
23.1L/h |
Fuel Consumption @ 100%
|
17.7L/h |
28.0L/h |
Engine model |
John Deere 4045HFG82 A |
John Deere 6068HFG82 A |
Speed regulation (RPM)
|
1500 | 1800 |
1500 | 1800 |
Starter Type |
Electric |
Electric |
Alternator model |
LEROY SOMER LSA44.3S3 |
LEROY SOMER LSA44.3L10 |
Alternator power |
88 | 106Kva |
165 | 199Kva |
Noise level |
55db |
60db |
Trailerised QES 16 | 20 | 40
Feature |
Trailerised QAS 16Kva |
Trailerised QAS 20Kva |
Trailerised QAS 40Kva |
Rated Frequency |
50hz |
50hz |
50hz |
Rated Voltage |
400 / 230V |
400 / 230V |
400 / 230V |
Prime Power Output |
13.7Kva |
20Kva |
42Kva |
Peak Power Output |
16Kva |
21.5Kva |
66Kva |
Rated Current |
20A |
29A |
61A |
Power Factor cos Phi |
0.8 |
0.8 |
0.8 |
Fuel Tank Capacity |
55L |
55L |
105L |
Fuel Autonomy @ 100% |
16h |
11h |
10h |
Fuel Consumption @ 25%
|
1.7L/h |
2.4L/h |
3.6L/h |
Fuel Consumption @ 50%
|
2.1L/h |
3.2L/h |
4.9L/h |
Fuel Consumption @ 75%
|
2.8L/h |
3.9L/h |
7.4L/h |
Fuel Consumption @ 100%
|
3.5L/h |
5.1L/h |
9.0L/h |
Engine model |
Kubota D1703 |
Kubota V2403 |
Kubota V3800 |
Speed regulation (RPM)
|
1500 |
1500 |
1500 |
Starter Type |
Electric |
Electric |
Electric |
Alternator model |
Mecc Alte |
Mecc Alte |
Mecc Alte |
Alternator power |
16Kva |
21.5Kva |
48Kva |
Control system make |
Deep Sea Electronics |
Deep Sea Electronics |
Deep Sea Electronics |
Control system model |
4620 AMF controller |
4620 AMF controller |
4620 AMF controller |
Noise level |
63db |
63db |
65db |
QES 180 | 250 Trailerised
QES 500 TwinPower
Feature |
QES 180 |
QES 250 Trailerised |
QES 500 |
Rated Frequency |
50hz |
50hz |
50hz |
Rated Voltage |
400V |
400V |
400V |
Prime Power Output |
180/144Kva |
250/200Kva |
500/400Kva |
Rated standby power (ESP) |
194/155Kva |
272/218Kva |
555/444Kva |
Rated Current |
259A |
360A |
721.7A |
Power Factor cos Phi |
0.8 |
0.8 |
0.8 |
Fuel Tank Capacity (24/48h) |
520/900L |
520/900L |
980L |
Fuel Autonomy @ 100% |
14.3 / 25h |
11.3 / 19.6h |
7.7h |
Fuel Consumption @ 100% |
36.5L/h |
46.0L/h |
127.6L/h |
Engine model |
6CTA8.3-G2 |
6LTAA8.9-G2 |
TAD1641GE |
Speed regulation (RPM) |
1500 |
1500 |
1500 |
Starter Type |
Electric |
Electric |
Electric |
Alternator model |
ACA270F |
ACA270J |
ACA355C |
Alternator power |
194/180Kva |
275/250Kva |
590/550Kva |
Control panel model |
DSE4620 |
DSE4620 |
DSE4520mkII |
Noise level |
73db |
77db |
78db |
Trailerised QAS 60/35 Variable Speed
Up to 40% less fuel consumption
Up to 40% less CO2 emissions
Trailerised QAS 65Kva
Feature |
Trailerised QAS 60/35 Variable Speed |
Trailerised 65Kva |
Rated Frequency |
50hz |
50hz |
Rated Voltage |
400 / 230V |
400 / 230V |
Prime Power Output |
35Kva |
63Kva |
Peak Power Output |
53Kva |
71Kva |
Rated Current |
260A (for 4 seconds) |
91A |
Power Factor cos Phi |
0.8 |
0.8 |
Fuel Tank Capacity |
260L |
160L |
Fuel Autonomy @ 100% |
27h |
22h |
Fuel Consumption @ 25%
|
2.6L/h |
4.5L/h |
Fuel Consumption @ 50%
|
4.3L/h |
7.0L/h |
Fuel Consumption @ 75%
|
6.8L/h |
9.6L/h |
Fuel Consumption @ 100%
|
9.5L/h |
12.3L/h |
Engine model |
Kubota V2403 |
John Deere 4045HF120 |
Speed regulation (RPM)
|
950 - 2550 |
1500 |
Starter Type |
Electric |
Electric |
Alternator model |
PMG-SK160C 16 |
Mecc Alte |
Alternator power |
32Kva |
71Kva |
Control system make |
Deep Sea Electronics |
Deep Sea Electronics |
Control system model |
4620 AMF controller |
4620 AMF controller |
Noise level |
66db |
65db |
Trailerised QAS 100Kva
Trailerised QAS 200Kva
Feature |
Trailerised 100Kva |
Trailerised 200Kva |
Rated Frequency |
50hz |
50hz |
Rated Voltage |
400 / 230V |
400 / 230V |
Prime Power Output |
105Kva |
197Kva |
Peak Power Output |
112Kva |
217Kva |
Rated Current |
148A |
284A |
Power Factor cos Phi |
0.8 |
0.8 |
Fuel Tank Capacity |
230L |
375L |
Fuel Autonomy @ 100% |
11h |
11h |
Fuel Consumption @ 25%
|
5.9L/h |
11.6L/h |
Fuel Consumption @ 50%
|
10.7L/h |
23.1L/h |
Fuel Consumption @ 75%
|
16.9L/h |
35.2L/h |
Fuel Consumption @ 100%
|
22.0L/h |
44.7L/h |
Engine model |
John Deere 4045HF120 |
John Deere 6068HFG20 |
Speed regulation (RPM)
|
1500 |
1500 |
Starter Type |
Electric |
Electric |
Alternator model |
Mecc Alte |
Mecc Alte |
Alternator power |
116Kva |
220Kva |
Control system make |
Deep Sea Electronics |
Deep Sea Electronics |
Control system model |
4620 AMF controller |
4620 AMF controller |
Noise level |
93db |
71db |
Trailerised QAS 325Kva
Trailerised QAS 500Kva
Feature |
Trailerised 325Kva |
Trailerised 500Kva |
Rated Frequency |
50hz |
50hz |
Rated Voltage |
400 / 230V |
400 / 230V |
Prime Power Output |
325Kva |
500Kva |
Peak Power Output |
341Kva |
550Kva |
Rated Current |
469A |
722A |
Power Factor cos Phi |
0.8 |
0.8 |
Fuel Tank Capacity |
1775L |
970L |
Fuel Autonomy @ 100% |
24h |
9h |
Fuel Consumption @ 25%
|
19L/h |
27.6L/h |
Fuel Consumption @ 50%
|
33.4L/h |
50.8L/h |
Fuel Consumption @ 75%
|
48.3L/h |
75.1L/h |
Fuel Consumption @ 100%
|
63.1L/h |
101.6L/h |
Engine model |
Volvo TAD 1341 GE |
Volvo TAD 1641 GE |
Speed regulation (RPM)
|
1500 |
1500 |
Starter Type |
Electric |
Electric |
Alternator model |
Leroy Somer |
Leroy Somer |
Alternator power |
341Kva |
570Kva |
Control system make |
Dief |
Dief |
Control system model |
QC 4003 Synchronizing Controller |
QC 4003 Synchronizing Controller |
Noise level |
69db |
69db |
QAC 1100 TwinPower Containerized Generator
QAC 1450 TwinPower Containerized Generator
Feature |
QAC 1100 TwinPower Containerized Generator |
QAC 1450 TwinPower Containerized Generator |
Rated Frequency |
50hz |
50hz |
Rated Voltage |
400 / 230V |
400 / 230V |
Prime Power Output |
1062Kva |
1590Kva |
Peak Power Output |
1000Kva |
1447Kva |
Rated Current |
1391A |
2013A |
Power Factor cos Phi |
0.8 |
0.8 |
Fuel Tank Capacity |
1640L |
1640L |
Fuel Autonomy @ 100% |
8h |
6h |
Fuel Consumption @ 25%
|
Depends on configuration |
Depends on configuration |
Fuel Consumption @ 50%
|
Depends on configuration |
Depends on configuration |
Fuel Consumption @ 75%
|
146L/h |
211L/h |
Fuel Consumption @ 100%
|
194L/h |
277L/h |
Engine model |
2x Scania DC13 072A |
2x Scania DC16 078A |
Speed regulation (RPM)
|
1500 |
1500 |
Starter Type |
Electric |
Electric |
Alternator model |
WEG |
WEG |
Alternator power |
550Kva each |
820Kva each |
Control system make |
Dief |
Dief |
Control system model |
QC 4003 Synchronizing Controller |
QC 4003 Synchronizing Controller |
Noise level |
74db |
n/a |
HiLight H6 Light Tower
Feature |
HiLight H6 |
Lamps |
LED |
Wattage |
4 x 350 |
Mast |
Hydraulic |
Max Height |
8m |
Max wind |
80km/h |
Light coverage m 2 |
6000 (average 20 luxes) |
Rated Frequency |
50hz |
Rated Voltage |
230V |
Operating temperature (min/max) |
-20 / 40ºC |
Energy source |
Diesel |
Engine model |
KubotaZ482 |
Fuel consumption Autonomy |
185h |
Fuel Tank Capacity |
125L |
Noise level |
55db |